BTU/hr and Refrigeration Tons: Understanding HVAC Power Units

NumberConvert Team9 min read

A comprehensive guide to BTU/hr, refrigeration tons, and HVAC power calculations. Learn how to size AC units, understand efficiency ratings like SEER and EER, and convert between power units.

Listen to this article

Browser text-to-speech

Why HVAC Power Units Matter

Whether you're replacing a home air conditioner, specifying equipment for a commercial building, or simply trying to understand your energy bills, HVAC power units can be confusing. The industry uses measurements like BTU/hr and refrigeration tons that seem archaic compared to watts and kilowatts. Understanding these units is essential for proper equipment sizing, energy cost calculations, and comparing different systems.

What is a BTU?

The British Thermal Unit (BTU) is a traditional unit of heat energy. Specifically, one BTU is the amount of energy needed to raise the temperature of one pound of water by one degree Fahrenheit at sea level. Despite its name suggesting British origin, the BTU is primarily used in the United States and a few other countries.

BTU/hr: The Power Measurement

While BTU measures energy (like joules or calories), HVAC systems are rated in BTU/hr (BTU per hour), which measures power—the rate of energy transfer. This is analogous to how electrical energy is measured in kilowatt-hours, but electrical power is measured in kilowatts.

Common BTU/hr ratings for residential AC units:

  • Window units: 5,000-25,000 BTU/hr
  • Portable AC: 8,000-14,000 BTU/hr
  • Mini-split systems: 9,000-36,000 BTU/hr
  • Central AC: 18,000-60,000 BTU/hr

When you see an air conditioner rated at "12,000 BTU," it actually means 12,000 BTU/hr—the rate at which it can remove heat from your space.

Refrigeration Tons Explained

The refrigeration ton (often just called "ton" in HVAC contexts) has a fascinating origin. In the era before mechanical refrigeration, ice harvested from frozen lakes was used to cool buildings and preserve food. The refrigeration industry needed a way to express cooling capacity that customers could understand.

The Definition

One refrigeration ton equals the cooling effect of melting one short ton (2,000 pounds) of ice over 24 hours. Since ice absorbs approximately 144 BTU of heat per pound when melting (the latent heat of fusion):

1 ton = 2,000 lbs x 144 BTU/lb / 24 hours = 12,000 BTU/hr

This elegant relationship—one ton equals exactly 12,000 BTU/hr—makes conversions straightforward.

Why Tons Are Still Used

Despite being based on 19th-century ice delivery, the ton remains standard for larger HVAC systems because:

  1. Convenient sizing: A 3-ton system is easier to discuss than a 36,000 BTU/hr system
  2. Industry convention: Contractors, engineers, and manufacturers all speak in tons
  3. Equipment categories: Residential systems typically range from 1.5 to 5 tons, making comparison simple

Converting Between HVAC Power Units

Understanding conversions helps you compare equipment and calculate energy costs.

Key Conversion Factors

FromToMultiply By
Refrigeration tonsBTU/hr12,000
BTU/hrRefrigeration tons0.0000833 (or divide by 12,000)
BTU/hrWatts0.293
WattsBTU/hr3.412
Refrigeration tonsKilowatts3.517
KilowattsRefrigeration tons0.284

Practical Examples

Example 1: A 3-ton central AC system

  • Cooling capacity: 3 x 12,000 = 36,000 BTU/hr
  • Equivalent to: 36,000 x 0.293 = 10,548 watts = 10.55 kW of cooling

Example 2: Converting a 24,000 BTU/hr mini-split to tons

  • 24,000 / 12,000 = 2 tons of cooling capacity

Example 3: A European heat pump rated at 7 kW cooling

  • 7 / 3.517 = 1.99 tons (essentially a 2-ton unit)
  • 7 x 3,412 = 23,884 BTU/hr

Use our BTU/hr to Watts converter or Refrigeration Tons to kW converter for quick calculations.

Sizing AC Units for Rooms and Buildings

Proper sizing is critical. An undersized system runs constantly without reaching the desired temperature. An oversized system short-cycles (turns on and off frequently), reducing efficiency, increasing wear, and failing to adequately dehumidify the space.

Quick Sizing Guidelines

For rough estimates, HVAC professionals often use these rules of thumb:

Basic calculation: 20-25 BTU per square foot

  • Standard room: 20 BTU/sq ft
  • Sunny rooms or warm climates: 25 BTU/sq ft
  • Well-insulated or shaded: 15-18 BTU/sq ft

Example: A 1,500 square foot home in a moderate climate

  • 1,500 x 20 = 30,000 BTU/hr
  • 30,000 / 12,000 = 2.5 tons

Most contractors would recommend a 2.5-ton or 3-ton system.

Factors That Affect Sizing

The simple square-footage calculation is just a starting point. Professional load calculations (using Manual J for residential or similar methods for commercial) account for:

  1. Climate zone: Phoenix needs more cooling than Seattle
  2. Insulation levels: Well-insulated homes need smaller systems
  3. Window area and orientation: Large south-facing windows increase load
  4. Ceiling height: Higher ceilings mean more volume to cool
  5. Occupancy: Each person adds roughly 400-600 BTU/hr
  6. Appliances and lighting: Kitchen equipment, computers, and lights generate heat
  7. Ductwork condition: Leaky or poorly insulated ducts reduce effective capacity

Room-by-Room Estimates

Room Size (sq ft)BTU/hr NeededEquivalent Tons
150-2505,000-6,0000.4-0.5
250-3507,000-8,0000.6-0.7
350-4509,000-10,0000.75-0.83
450-55011,000-12,0000.9-1.0
550-70013,000-14,0001.1-1.2
700-1,00018,000-21,0001.5-1.75

Energy Efficiency Ratings: SEER and EER

Understanding efficiency ratings helps you compare equipment and estimate operating costs.

EER (Energy Efficiency Ratio)

EER measures efficiency at a specific condition: 95 degrees F outdoor temperature, 80 degrees F indoor temperature, and 50% relative humidity. The formula is simple:

EER = Cooling Output (BTU/hr) / Power Input (Watts)

A 12,000 BTU/hr unit drawing 1,200 watts has an EER of 10.

Higher EER means better efficiency. Window units typically range from 8 to 12 EER, while high-efficiency central systems can exceed 14 EER.

SEER (Seasonal Energy Efficiency Ratio)

SEER provides a more realistic picture by averaging efficiency across an entire cooling season with varying temperatures. It's calculated using outdoor temperatures ranging from 65 degrees F to 104 degrees F, weighted by typical occurrence.

Minimum SEER requirements (as of 2023):

  • Northern US: 14 SEER
  • Southern US: 15 SEER

Efficiency tiers:

SEER2: The New Standard

Starting in 2023, the US adopted SEER2, which uses updated testing procedures with more realistic duct conditions (higher external static pressure). SEER2 ratings are typically 4-5% lower than SEER for the same equipment.

Comparison:

  • A unit rated 16 SEER might be rated 15.2 SEER2
  • A 20 SEER unit might be rated 19 SEER2

When comparing equipment, ensure you're using the same rating system.

Calculating Energy Costs

Estimated annual cooling cost:

Annual kWh = (Cooling Load x Cooling Hours) / (SEER x 1,000)

Example: A 3-ton (36,000 BTU/hr) system running 1,500 hours annually

With 14 SEER:

  • (36,000 x 1,500) / (14 x 1,000) = 3,857 kWh
  • At $0.15/kWh = $579/year

With 20 SEER:

  • (36,000 x 1,500) / (20 x 1,000) = 2,700 kWh
  • At $0.15/kWh = $405/year

The high-efficiency unit saves approximately $174 annually.

Commercial vs Residential HVAC Sizing

Commercial HVAC differs significantly from residential systems in scale, complexity, and sizing methodology.

Residential Systems

Typical range: 1.5 to 5 tons

Most homes use split systems with an outdoor condenser and indoor air handler, or packaged rooftop units. Sizing follows Manual J calculations, and systems are usually sized to handle peak load conditions.

Commercial Systems

Typical range: 5 to 400+ tons

Commercial buildings use various system types:

  1. Rooftop units (RTUs): 3-50 tons, common for retail and small offices
  2. Split systems: 5-20 tons, used for specific zones
  3. Variable Refrigerant Flow (VRF): 6-60 tons per system, highly efficient for multi-zone buildings
  4. Chillers: 50-4,000+ tons, for large buildings and campuses
  5. Cooling towers: Used with chillers for heat rejection

Commercial Sizing Considerations

Commercial load calculations (often using Manual N or computerized energy modeling) account for:

  • Diverse usage patterns: Unlike homes, commercial buildings have varying occupancy throughout the day
  • Internal heat gains: Computers, lighting, and equipment generate significant heat
  • Ventilation requirements: Commercial codes require more outdoor air per occupant
  • Zoning needs: Different areas may have different cooling requirements
  • Redundancy: Critical facilities may require backup capacity

Square Footage Guidelines by Building Type

Building TypeBTU/sq ftTons per 1,000 sq ft
Office (interior)25-352.1-2.9
Office (perimeter)35-452.9-3.75
Retail30-402.5-3.3
Restaurant40-603.3-5.0
Hospital35-502.9-4.2
Data center100-3008.3-25

These are rough guidelines—actual loads depend on specific building characteristics.

Key Takeaways

  1. BTU/hr measures cooling rate: One BTU is the energy to heat one pound of water by one degree F; BTU/hr is the power unit used for HVAC equipment

  2. One refrigeration ton = 12,000 BTU/hr: This relationship comes from the heat absorbed when melting one ton of ice in 24 hours

  3. Conversion to metric: 1 ton = 3.517 kW; BTU/hr x 0.293 = watts

  4. Sizing rule of thumb: 20-25 BTU per square foot, but professional load calculations consider many additional factors

  5. Efficiency matters: A 20 SEER system uses about 30% less electricity than a 14 SEER system for the same cooling output

  6. Residential vs commercial: Home systems typically range from 1.5-5 tons; commercial buildings may require hundreds of tons across multiple systems

  7. Get professional sizing: Oversized or undersized equipment wastes energy, increases wear, and provides poor comfort. Always have a qualified contractor perform load calculations for new installations.

See what our calculators can do for you

Ready to take control of your finances?

Explore our free financial calculators and tools to start making informed decisions today.

Explore Our Tools

Frequently Asked Questions

Common questions about the BTU/hr and Refrigeration Tons: Understanding HVAC Power Units

BTU (British Thermal Unit) measures energy—the amount of heat needed to raise one pound of water by one degree Fahrenheit. BTU/hr measures power—the rate of energy transfer per hour. HVAC equipment is rated in BTU/hr because it describes how quickly the system can add or remove heat, not just the total amount of energy.
BTU/hr and Refrigeration Tons: Understanding... | FinToolset